Modular Data Center Quote: 23 Questions Worth Asking

A modular data center quote is harder to compare than it looks. Two vendors can price the same requirement and land a factor of two apart, with both quotes honest, because they drew the scope boundary in different places and assumed different conditions.

These are the questions that surface the difference. Take them to every vendor, including us.

Scope: what is actually in the box

  1. Is the cooling plant included, and are external condensers or dry coolers inside or outside the price?
  2. Is a UPS included, and at what runtime?
  3. Are switchgear and the transformer included or excluded?
  4. Is a generator included, and the automatic transfer switch with it?
  5. Are racks, PDUs and internal distribution included, and to what rack count?
  6. Is fire detection and suppression inside the unit included?
  7. Is physical security hardware, access control and monitoring included?
modular data center quote

Site works: what you are expected to provide

  1. Is the foundation or pad in scope, and whose design is it?
  2. Is crane and rigging included on delivery day?
  3. Is utility tie-in labour included, and up to what distance?
  4. Is shipping included, and for non-standard enclosures are oversize permit costs estimated?
  5. Who provides stamped drawings if the authority having jurisdiction requires them?

Items 8 to 12 are where most of the gap between two quotes lives. Our guide to data center site preparation covers what the buyer normally carries.

Assumptions that change the machine

  1. What site design ambient temperature was assumed, and from what source?
  2. What rack density does the quote assume, average and peak?
  3. Is the cooling approach air, liquid, or hybrid, and is liquid in scope now or later?
  4. What redundancy level is quoted: N, N+1 or 2N, and what does it cover?
  5. What service voltage and phase does the quote assume at the point of connection?

Item 13 is the one buyers most often skip and most often regret. A modular data center quote built around a 95F design day is a different product from one built around 110F, and the price gap is real engineering rather than margin.

modular data center quote

Schedule, testing and what happens after

  1. Is the quoted lead time measured order to factory acceptance, or order to ready for service? Contract type shapes how firm that date is, and FAR Part 16 sets out the options on federal work.
  2. Are long-lead components already on order, or does the clock start at your purchase order?
  3. Is factory acceptance testing included, and may you attend?
  4. Are site acceptance and integrated systems testing included?
  5. What warranty period applies, to the enclosure and to the plant inside it, and is an extended term priced?
  6. Is remote monitoring included or an additional subscription?

Question 18 alone can move an apparent delivery date by months. The two measures are not the same and vendors do not use them consistently.

How to use the answers

Put the responses in a table, one column per vendor, one row per question. Normalise before you compare: add the excluded items back into the cheaper quote at your own estimate, and only then look at the totals. A modular data center quote that excludes the transformer, the generator and the pad is not cheaper, it is narrower.

If a vendor will not answer a question in writing, treat that as the answer.

Frequently asked questions

What should a modular data center quote include?

At minimum the enclosure, racks and internal distribution, with the cooling plant specified. Switchgear, transformer, generator, pad, crane and utility tie-in are commonly excluded, so confirm each one explicitly rather than assuming.

Why do two modular data center quotes differ so much?

Usually scope boundary and assumptions rather than margin. Different design ambient temperatures, redundancy levels and rack densities produce genuinely different machines, and excluded site works shift large costs from one column to another.

What is the difference between order to FAT and order to RFS?

Order to factory acceptance testing measures when the unit is built and tested in the factory. Order to ready for service measures when it is live on your site. The gap includes shipping, setting, tie-in and commissioning, and can be months.

Should I ask for design ambient temperature in a quote?

Yes, always. It determines the cooling plant and therefore a significant part of the price. Two quotes assuming different design ambients are not comparable, and neither vendor is necessarily wrong.

Who normally pays for the crane?

It varies, which is why it belongs on the list. Crane and rigging fall between the manufacturer and the site works contractor more often than any other single item.

How do I compare quotes with different scopes?

Normalise first. Add the missing items back into the narrower quote at your own estimate, then compare totals. Comparing headline figures across different scopes is the most common costing error in this category.

Where to go next

The cost guide explains why per-megawatt figures mislead below a megawatt, and the container line shows what a standard product looks like from 7 ft to 52 ft. If you want these answered against a real requirement, send it over.

Tell us your site, power and timeline.

Send the load you need to support, the power and ground you have, and the date it has to be live. We will tell you which length fits and what the schedule looks like.